<?xml version="1.0" encoding="utf-8"?>
<Spec id="490" path="\8\c\8c5537af6716b9d3e0b9f8f4e17d7c03.pdf"><Text id="84671" page="6">All the materials used for Facility shall be new and in Compliance to ASME Sec II, (Materials). Equipment in Sour Service shall comply with NACE MR-0175/ISO 15156. In addition to this HIC testing shall be performed in accordance with NACE TM 0284 for wetted parts of carbon steel plates, welded pipes and welded fittings.</Text><Text id="84672" page="6">Welding and NDT shall be per KOC standard KOC-MW-001 and/ or ASME Sec IX, ASME Sec V.</Text><Text id="84673" page="6">All packaged systems shall consist of Piping, Valves, Electrical, Instrumentation and Controls as per respective Discipline Technical Specifications.</Text><Text id="84674" page="6">The elevation of PSV nozzles shall be such that it is located higher than the elevation of Flare Gas Header with a minimum slope of 1:500 of Flare Gas Header connecting line.</Text><Text id="84675" page="6">All equipment inside the packaged units shall be designed as per respective KOC Standards and / or International Standards as specified in the clauses below.</Text><Text id="84676" page="6">Safety Ladders, Cage and Gate will be coated with different color, preferably yellow for easy identification.</Text><Text id="84696" page="6">Wind load and seismic load shall be as per KOC standards KOC-C-001 and KOC-G- 007.</Text></Spec>