<Spec id="541" path="\8\2\82de9013a3483805b4c90ccf890022ea.pdf"><Text id="85354" page="23">15.1. ESD &amp; Control valves shall be designed, installed and tested in compliance with KOC-I-010. Actuators for ESDV shall be spring return pneumatic cylinder actuators. ESDV shall be fitted with smart positioner to allow partial stroke testing (PST) for predictive maintenance purposes, only wherever recommended in SIL assessment &amp; verification studies.</Text><Text id="85356" page="23">15.2. Partial stroke requirement shall be based on the Test interval as recommended in the SIL assessment and SIL verification study. Such ESDVs shall be supplied with partial stroke testing facility from the control room. ESDVs shall form a part of the Safety Instrumented Function (SIF) and shall comply with the SIL design requirements.</Text><Text id="86680" page="23">. ESD &amp; Control valves shall be designed, installed and tested in compliance with KOC-I-010. Actuators for ESDV shall be spring return pneumatic cylinder actuators. ESDV shall be fitted with smart positioner to allow partial stroke testing (PST) for predictive maintenance purposes, only wherever recommended in SIL assessment &amp; verification studies.</Text></Spec>